1.1 Structure
Please provide a
(W) x
(L) x
(H) UL classified prefabricated modular structure
for interior use manufactured by Allied Modular Building Systems, Inc.
or equal. Building is shipped disassembled with all hardware for onsite
assembly.
1.2 Installation
Please provide installation, delivery and pre-wire for the above structure.
This includes all travel, installation, labor and any other expenses that
may be incurred to install the walls, doors, ceiling and other non-electrical
items.
1.2a Pre-wire
Please provide all electrical wiring of all outlets, lights, switches
and any other electrical components that are required on this project.
All concealed electrical shall be encased in flexible aluminum or steel
conduit. All exposed conduit shall be encased in steel conduit. All components
shall be wired to a load center / sub panel or one location within the
proposed structure. If wiring to the load center / sub panel, it shall
be wired to breakers that are also provided. All wiring must be field-tested.
All wiring shall be completed with 12 GA. minimum THHN Type and shall
comply with all N.E.C. requirements. All circuits shall be 20 amp single
pole or 20 amp 2-pole breakers. A ground wire shall be pulled to all lights,
outlets and any other electrical component. This does not include main
electrical hookup or phone and data jacks to the main board.
Note: Modular Wiring is not acceptable.
1.3 Freight
Please provide freight to our plant. This includes all freight charges
from your facility to ours. The shipper shall file any damages or freight
claims. No additional purchase orders for damaged materials will be accepted.
The recipient shall incur no costs for freight claims. This shall include
all charges for freight, damage, insurance, fuel surcharges and any other
costs that may be incurred. This does not include unloading at the destination
facility.
MATERIALS
2.1 Wall Panels 2"
The wall shall be 2" actual thickness minimum Combustible or Non-Combustible.
The entire wall system shall be approved by UL (Underwriters Laboratory).
Panels shall be modular and interchangeable with a minimum thickness on
1-7/8" overall width. The panel shall consist of an insulated rigid
polystyrene core permanently laminated to a noncombustible gypsum board
or other noncombustible materials. Heavy-duty vinyl laminated facing shall
be permanently applied at the factory and shall be easily cleanable. The
panels shall be fully fabricated at the factory for easy installation.
No splicing shall be necessary for any panels under 10' total height.
All panels will be UL Classified and meet a class "A" fire rating
which requires a minimum of 0-25 flame spread. The make-ups are as follows:
a. Vinyl Laminated Gypsum with a rigid polystyrene foam core. b. Vinyl Laminated Hardboard with a rigid polystyrene foam core. c. FRP laminated with a rigid polystyrene foam core. d. Aluminum Embossed Pebble Texture painted skin with a rigid polystyrene
foam core. e. Steel Embossed Pebble Texture Paint Lock skin with a rigid polystyrene
foam core.
2.3 Base Channel
The base channel shall be anodized aluminum or painted aluminum with a
minimum thickness of .080. The base channel shall be anchored at 48"
O.C. with 1/2" x 3-1/2" minimum embedded wedge anchors or per
engineers specifications. Anchors shall be included with materials.
2.4 Posts and Framing (Non-Progressive)
Posts shall be anodized aluminum framing channels with minimum temper
strength of 6063-T5. The posts will allow a load to 3,500 lbs but not
to exceed 4,000 lbs. Each post shall be an intricate part of the structure.
The channel shall consist of three parts and allow the ability to remove
any panel without disturbing adjacent panels. The connecting posts shall
serve as an electrical raceway accommodating electrical, data and phone.
2.5 Posts and Framing (Progressive)
Posts shall be anodized aluminum framing channels with minimum temper
strength of 6063-T5. The posts will allow for a load to 3,500 lbs but
not to exceed 4,000 lbs. Each post shall be an intricate part of the structure.
The connecting posts shall serve as an electrical raceway accommodating
electrical, data and phone. The raceway shall bear a UL Classified sticker
and conform to all UL reports.
2.6 Windows - (Single Pane)
Windows shall be installed in panels per customer drawing. Windows shall
be of the picture-window type or sliding window type per customer drawing.
The window glass shall be a minimum 3/16-inch thick clear tempered safety
glass pre mounted in an aluminum frame. Windows shall be a nominal 40
inches in height and extend across the full width of its supporting panel.
The windowsill height shall 41 inches from the floor. The sliding windows
shall be able to slide horizontally. The sliding windows shall have locks
lockable from the inside of the modular office. Weather stripping shall
also be provided with the sliding windows.
2.8 Panel Caps
Anodized aluminum panel caps or manufacturer's standard panel caps incorporating
a vertical fascia shall be installed securely on the top perimeter of
the wall panels. The panel caps shall provide a neat appearance where
the wall panels and roof deck come together.
3.0 Doors
All doors shall be pre-hung at the factory and assembled into wall panels
to ensure easy installation and proper fit. Doors shall be a nominal 36
inches wide by 80 inches high and have thickness of 1-3/4 inches. The
interior and exterior finish of the doors shall be color coordinated with
the exterior finish of the wall panels All doors shall have the same finish
on both sides. The door type are as follows:
a. 3068 Hollow core door with standard hinges and knob b. 3068 Solid core door with standard hinges and knob c. Steel door with standard hinges and knob. Powder coated to coordinate
with wall color. d. 6068 double door with (2) 3068 Hollow core doors with standard
hinges and knob
and flush mounted bolts e. 6068 double door with (2) 3068 Solid core doors with standard
hinges and knob
and flush mounted bolts f. 6068 double door with (2) 3068 Steel doors with standard hinges
and knob
and flush mounted. Powder coated to coordinate with wall color.
3.1 Single Vision Lite / Window in Door (Single pane)
The upper half of all doors shall have a 20" x 24" picture window
with a minimum 3/16" thick clear tempered safety glass. Rubber shall
be placed on the inside of all openings.
3.2 Single Vision Lite / Window in Door (Dual Pane)
The upper half of all doors shall have a 20" x 24" picture window
with a minimum 3/16- Inch thick clear tempered safety glass. Rubber shall
be placed on the inside of all openings.
4.0 Roof Deck
The roof deck shall be galvanized roll-formed ribbed steel interlocking
panels. The roof deck panels shall be a minimum of 20-gauge thickness.
Panels shall be designed to achieve optimum structural efficiency. The
roof deck shall span the full length and width of the modular office and
hold a minimum of 10 psf live load and 10 psf dead load and shall conform
to Seismic Zone 4 requirements.
5.0 Hardware
Hardware shall be Allied Modular Standard.
6.0 Ceiling
The ceiling shall be suspended from the roof deck and supported by the
wall perimeter or in accordance with the manufacturer's standard installation
procedures. The suspended ceiling shall consist of white enameled T-bar
ceiling grid hung from hanger tabs and 12 gauge wires, mineral fiber tiles
with a random-fissured finish. The ceiling panels shall be 2 feet wide
by 4 feet long by minimum 5/8-inch thick lay-in acoustical panels or equivalent.
The ceiling structure shall meet UL Class A Fire Rating with 0-25 flame
spread. The T-bar ceiling grid shall provide support for the light fixtures
and shall be supported at each corner of each light fixture.
6.1 Cleanroom Ceiling
The ceiling shall be suspended from the roof deck and supported by the
wall perimeter or in accordance with the manufacturer's standard installation
procedures. The suspended ceiling shall consist of white enameled T-bar
ceiling grid hung from 12 gauge hanger tabs and wires, white vinyl-faced
gypsum with a easily cleanable finish. The ceiling panels shall be 2 feet
wide by 4 feet long by minimum 5/8-inch thick lay-in acoustical panels
or equivalent. The ceiling structure shall meet UL Class A Fire Rating
with 0-25 flame spread. The T-bar ceiling grid shall provide support for
the light fixtures and shall be supported at each corner of each light
fixture
7.0 Heat / Air Conditioner and Opening
Appropriate size wall mounted A/C or HVAC shall be provided in accordance
with all local mechanical codes. A Heating/Ventilation/Air Conditioner
(HVAC) panel shall be located per customer. The HVAC opening shall be
of solid construction. The HVAC opening shall be reinforced to support
a minimum 150 -pound wall mounted HVAC unit and shall be lined with aluminum
trim. There shall be at least 60 inches between the floor and the bottom
of the HVAC opening.
8.0 Light Fixtures T-12
Light fixtures shall be recessed in the ceiling. The lay-in light fixtures
shall be 2 feet wide by 4 feet long and incorporate T12 4100K lamps with
electronic ballasts. Light fixtures shall have a minimum 128-watt capacity
and be equipped with diffuser lens. The appropriate quantity of light
fixtures shall be located in the ceiling such that a minimum of 50-foot
candles lighting at a height of 3 feet from the floor is evenly maintained
throughout the modular office. Tubes are not included.
8.1 Light Fixtures T-8
Light fixtures shall be recessed in the ceiling. The lay-in light fixtures
shall be 2 feet wide by 4 feet long and incorporate T8 4100K lamps with
electronic ballasts. Light fixtures shall have a minimum 128-watt capacity
and be equipped with diffuser lens. The appropriate quantity of light
fixtures shall be located in the ceiling such that a minimum of 50-foot
candles lighting at a height of 3 feet from the floor is evenly maintained
throughout the modular office. Tubes are not included.
8.2 Light Switches
A light switch shall be provided at each doorway. Light switches shall
be located on the interior wall and opposite the door hinges. Light switches
shall be conveniently placed for easy access. Light switches shall be
located 42 inches in height from the floor. Light switches shall be provided
with cover plates. Light switches shall conform to the National Electric
Code.
8.3 Electrical Outlets
Wall outlets shall be standard 110-volt AC duplex outlets. Wall outlets
shall be located as shown on drawings. Wall outlets shall be a nominal
18 inches in height from the floor. A 230-volt outlet shall be installed
near the HVAC opening at a height of at least sixty inches to interface
with the HVAC power cords. All outlets shall be provided with cover plates.
Outlets shall conform to the National Electric Code.
OTHER
10.0 Warranty
All materials shall be guaranteed to be free of manufacturing defects
for a period of 10 years from the date of shipment. All workmanship shall
be guaranteed to be free of defects for a period of 1 year from the date
of shipment. For items not manufactured by Allied Modular, the manufacturers
warranty applies. Installation is not covered under warranty unless provided
by Allied Modular's factory trained installers.