Please provide a
(W) x
(L) x
(H) UL Classified prefabricated modular structure for exterior use manufactured
by Allied Modular Building Systems, Inc. or equal. Building to be shipped
disassembled with all hardware for onsite assembly.
1.2 INSTALLATION
Please provide me
with installation, delivery, and pre-wire for the above structure. This
includes all travel, installation, labor, and any other expenses that
may be incurred to install the walls, doors, ceiling and other non electrical
items.
PRE-WIRE
Please provide me with all electrical wiring of all outlets, lights,
switches, and any other electrical components that are required on this
project. All concealed electrical shall be encased in flexible aluminum
or steel conduit. All exposed conduit shall be encased in steel conduit.
All components shall be wired to a load center /sub panel or one location
within the proposed structure. All wiring to the load center / Sub panel
shall be wired to breakers that are also provided. All wiring must be
field-tested. All wiring shall be consist of 12 GA. minimum THHN Type
and shall comply with all N.E.C. requirements. All circuits shall be
20 amp single pole or 20 amp 2-pole breakers. A ground wire shall be
pulled to all lights, outlets, and any other electrical component. This
does not include main electrical hookup or phone and data jacks to the
main board.
Note: Modular Wiring is not acceptable.
1.3 FREIGHT
Please provide freight to our facility. Include all freight charges
from your facility to ours. Any damages or freight claims shall be filed
by the shipper. No additional purchase orders for damaged materials
will be accepted. The recipient shall incur no costs for freight claims.
This shall include all charges for freight, damage, insurance, fuel
surcharges and any other costs that may be incurred. This does not include
unloading at the destination facility.
MATERIALS
2.1 WALL PANELS 2”
The wall shall be 2” actual thickness minimum combustible or
noncombustible. The entire wall system shall be approved by UL (Underwriters
Laboratory).
Panels shall be modular and interchangeable with a minimum thickness
on 2” overall width. The standard panel shall consist of an insulated
rigid polystyrene core permanently laminated between two sheets of noncombustible
stucco embossed tempered hardboard. The panels shall be fully fabricated
at the factory for easy installation. No splicing shall be necessary
for any panels under 10’ total height. All panels will be UL
approved and meet a class “A” fire rating which requires
a minimum of 0-25 flame spread. The panel types are as follows:
a. Stucco Embossed Tempered Hardboard with a rigid polystyrene foam
core.
b. Aluminum Embossed Pebble Texture painted skin with a rigid polystyrene
foam core.
c. Steel Embossed Pebble Texture Painted Skin with a rigid polystyrene
foam core.
2.3 BASE CHANNEL
The base channel shall be anodized aluminum or painted aluminum with
a minimum thickness of .080. The base channel shall be anchored at 24”
O.C. with ½” x 3-1/2” minimum embedded wedge anchor
or per engineers specifications. Anchors shall be included with materials.
2.4 POSTS & FRAMING ( NON PROGRESSIVE)
Posts shall be anodized aluminum framing channels with minimum temper
strength of 6063-T5. The posts will allow a load to 3,500 lbs., but
not to exceed 4,000 each and shall be an intricate part of the structure.
The channel shall consist of three parts and allow the ability to remove
any panel without disturbing adjacent panels. The connecting posts shall
serve as an electrical raceway accommodating electrical, data and phone.
2.5 POSTS & FRAMING (PROGRESSIVE)
Posts shall be anodized aluminum framing channels with minimum temper
strength of 6063-T5. The posts will allow for a load to 3,500 lbs.,
but not to exceed 4,000 each and shall be an intricate part of the structure.
The connecting posts shall serve as an electrical raceway accommodating
electrical, data and phone. The raceway shall bear a UL Classified sticker
and conform to all UL reports.
2.6 WINDOWS-(SINGLE PANE)
Windows shall be installed in panels per customer drawing. Windows shall
be of the picture-window type or sliding window type per customer drawing.
The window glass shall be a minimum 3/16-inch thick clear, tempered
safety glass pre mounted in an aluminum frame. Windows shall be a nominal
40 inches in height and extend across the full width of its supporting
panel. The window sill height shall be 41 inches from the floor. The
sliding windows shall be able to slide sideways. The sliding windows
shall have locks lockable from the inside of the modular office. Weather
stripping shall also be provided with the sliding windows.
2.8 PANEL CAPS
Anodized aluminum panel caps or manufacturer’s standard panel
caps incorporating a vertical fascia shall be installed securely on
the top perimeter of the wall panels. The panel caps shall provide a
neat appearance where the wall panels and roof deck come together.
3.0
DOORS
All doors
shall be pre-hung at the factory and assembled into panels to ensure
easy installation and proper fit. Doors shall be a nominal 36 inches
wide by 80 inches high and have thickness of 1-3/4 inches. The interior
and exterior finish of the doors shall be color coordinated with the
exterior finish of the wall panels. All doors shall have the same finish
on both sides. The type of door is as follows:
a. 3068 Solid
core door with standard hinges and knob.
b. 3068 Steel
door with standard hinges and knob. Powder coated to coordinate with
wall color.
3.1
SINGLE VISION LITE / WINDOW IN DOOR (Single pane)
The upper half of all doors shall have a 20" x 24" with a
minimum 3/16- Inch thick clear tempered safety glass picture-window.
Rubber shall be placed on the inside of all openings
3.1 SINGLE VISION LITE / WINDOW IN DOOR (Dual Pane)
The upper half of all doors shall have a 20" x 24" with a
minimum 3/16- Inch thick clear tempered safety glass picture-window.
Rubber shall be placed on the inside of all openings.
4.0 PANELIZED ROOF SYSTEM
The roof system shall be a aluminum roll-formed interlocking panel.
The roof deck panels shall be a minimum of .19 gauge thickness with
a rigid polystyrene core permanently laminated to aluminum skin. Panels
shall be designed to achieve optimum structural efficiency. The Panelized
roof shall span the full width of the modular guard house and hold a
minimum of 30 psf. live load and 10 psf. dead load and shall conform
to seismic zone 4 requirements. The roof shall be installed with a minimum
of 1/4” per ft grade on the overall span.
5.0 HARDWARE
Hardware shall be Allied Modular Standard.
6.0 CEILING
The ceiling shall be suspended from the roof deck and supported by the
wall perimeter or in accordance with the manufacturer’s standard
installation procedures. The suspended ceiling shall consist of white
enameled T-bar ceiling grid hung from hanger tabs and 12 gauge wires,
mineral fiber tiles with a random-fissured finish. The ceiling panels
shall be 2 feet wide by 4 feet long by minimum 5/8-inch thick lay-in
acoustical panels or equivalent. The ceiling structure shall meet UL
Class A Fire Rating with 0-25 flame spread. The T-bar ceiling grid shall
provide support for the light fixtures and shall be supported at each
corner of each light fixture.
6.1 CLEANROOM CEILING
The ceiling shall be suspended from the roof deck and supported by the
wall perimeter or in accordance with the manufacturer’s standard
installation procedures. The suspended ceiling shall consist of white
enameled T-bar ceiling grid hung from 12 gauge hanger tabs and wires,
white vinyl-faced gypsum with cleanable finish. The ceiling panels shall
be 2 feet wide by 4 feet long by minimum 5/8-inch thick lay-in acoustical
panels or equivalent. The ceiling structure shall meet UL Class A Fire
Rating with 0-25 flame spread. The T-bar ceiling grid shall provide
support for the light fixtures and shall be supported at each corner
of each light fixture.
7.0 HEAT / AIR CONDITIONER & OPENING
Appropriate size wall mounted A/C or HVAC shall be provided in accordance
with all local mechanical codes. A Heating/Ventilation/Air Conditioner
(HVAC) panel shall be located per customer. The HVAC opening shall be
of solid construction. The HVAC opening shall reinforced to support
a minimum 150 pound wall mounted HVAC unit and shall be lined with aluminum
trim. There shall be at least 60 inches between the floor and the bottom
of the HVAC opening.
8.0 LIGHT FIXTURES - T12
Light fixtures shall be recessed in the ceiling. The lay-in light fixtures
shall be 2 feet wide by 4 feet long and incorporate T12 4100K lamps
with electronic ballasts. Light fixtures shall have a minimum 128-watt
capacity and be equipped with diffuser lens. The appropriate quantity
of light fixtures shall be located in the ceiling such that a minimum
of 50-foot candles lighting at a height of 3 feet from the floor is
evenly maintained throughout the modular office. Tubes shall be provided
by other.
8.1 LIGHT FIXTURES - T8
Light fixtures shall be recessed in the ceiling. The lay-in light fixtures
shall be 2 feet wide by 4 feet long and incorporate T8 4100K lamps with
electronic ballasts. Light fixtures shall have a minimum 128-watt capacity
and be equipped with diffuser lens. The appropriate quantity of light
fixtures shall be located in the ceiling such that a minimum of 50-foot
candles lighting at a height of 3 feet from the floor is evenly maintained
throughout the modular office. Tubes shall be provided by other.
8.1.1 LIGHT SWITCHES
A light switch shall be provided at each doorway. Light switches shall
be located on the interior wall and opposite the door hinges. Light
switches shall be conveniently placed for easy access. Light switches
shall be located 42 inches in height from the floor. Light switches
shall be provided with cover plates. Light switches shall conform to
the National Electric Code.
8.2 ELECTRICAL OUTLETS
Wall outlets shall be standard 110-volt AC duplex outlets. Wall outlets
shall be located as shown on drawings. Wall outlets shall be a nominal
18 inches in height from the floor. A 230-volt outlet shall be installed
near the HVAC opening at a height of at least sixty inches to interface
with the HVAC power cords. Outlets shall be provided with cover plates.
Light switches shall conform to the National Electric Code.
OTHER
9.0 FORKLIFTABLE STEEL BASE
A forkliftable steel base shall be constructed of heavy duty steel C-channel
with appropriate size supports to handle building size. The base shall
be equipped with forklift sleeves to enable the lifting of the entire
completed unit. The top of the base shall be 1-1/8” T&G Plywood.
Floor tile is optional.
10.0
WARRANTY
All workmanship
shall be guaranteed to be free of defects for a period of one year from
the date of shipment. All materials to be free of manufacturers defect
for ten years from the date of shipment. For items not manufactured
by Allied Modular, the manufacturers warranty applies. Installation
is not covered under warranty unless provided by Allied Modular's factory
trained installers.