1.2 Installation
Please provide me with installation, delivery, and pre-wire for the
above structure. This includes all travel, installation, labor, and
any other expenses that may be incurred to install the walls, doors,
ceiling and other non-electrical items.
Pre-Wire
Please provide me with all electrical wiring of all outlets, lights,
switches, and any other electrical components that are required on this
project. All concealed electrical shall be encased in flexible aluminum
or steel conduit. All exposed conduit shall be encased in steel conduit.
All components shall be wired to a load center /sub panel or one location
within the proposed structure. All wiring to the load center / Sub panel
shall be wired to breakers that are also provided. All wiring must be
field-tested. All wiring shall be consist of 12 GA. minimum THHN Type
and shall comply with all N.E.C. requirements. All circuits shall be
20 amp single pole or 20 amp 2-pole breakers. A ground wire shall be
pulled to all lights, outlets, and any other electrical component. This
does not include main electrical hookup or phone and data jacks to the
main board.
Note: Modular Wiring
is not acceptable.
1.3 Freight
Please provide freight to our facility. Include all freight charges
from your facility to ours. The shipper shall file any damages or freight
claims. No additional purchase orders for damaged materials will be
accepted. The recipient shall incur no costs for freight claims. This
shall include all charges for freight, damage, insurance, fuel surcharges
and any other costs that may be incurred. This does not include unloading
at the destination facility.
Materials
2.1 Wall
Panels – 4”
The wall shall be 4” actual thickness minimum Combustible or noncombustible.
The entire wall system shall be approved by UL (Underwriters Laboratory).
Panels shall be
modular and interchangeable with a minimum thickness on 3-1/2”
overall width. The standard panel shall consist of an insulated rigid
polystyrene core permanently laminated between two sheets of noncombustible
stucco embossed tempered hardboard. The panels shall be fully fabricated
at the factory for easy installation. No splicing shall be necessary
for any panels under 10’ total height. All panels will be UL Classified
and meet a class “A” fire rating which requires a minimum
of 0-25 flame spread. The panel types are as follows:
a. Stucco Embossed
Tempered Hardboard with a rigid polystyrene foam core.
b. Aluminum Embossed Pebble Texture painted skin with a rigid polystyrene
foam core.
c. Steel Embossed Pebble Texture Painted Skin with a rigid polystyrene
foam core.
2.3 Base
Channel
The base channel shall be anodized aluminum or painted aluminum with
a minimum thickness of .080. The base channel shall be anchored at 24”
O.C. with ½” x 3-1/2” minimum embedded wedge anchor
or per engineers specifications. Anchors shall be included with materials.
2.4 Posts
& Framing ( Non Progressive)
Posts shall be anodized aluminum framing channels with minimum temper
strength of 6063-T5. The posts will allow a load to 3,500 lbs., but
not to exceed 4,000 each and shall be an intricate part of the structure.
The channel shall consist of three parts and allow the ability to remove
any panel without disturbing adjacent panels. The connecting posts shall
serve as an electrical raceway accommodating electrical, data and phone.
2.5 Posts
& Framing (Progressive)
Posts shall be anodized aluminum framing channels with minimum temper
strength of 6063-T5. The posts will allow for a load to 3,500 lbs.,
but not to exceed 4,000 each and shall be an intricate part of the structure.
The connecting posts shall serve as an electrical raceway accommodating
electrical, data and phone. The raceway shall bear a UL Classified sticker
and conform to all UL reports.
2.6 Windows-
(Single Pane)
Windows shall be installed in panels per customer drawing. Windows shall
be of the picture-window type or sliding window type per customer drawing.
The window glass shall be a minimum 3/16-inch thick clear, tempered
safety glass pre mounted in an aluminum frame. Windows shall be a nominal
40 inches in height and extend across the full width of its supporting
panel. The windowsill height shall be 41 inches from the floor. The
sliding windows shall be able to slide sideways. The sliding windows
shall have locks lockable from the inside of the modular office. Weather
stripping shall also be provided with the sliding windows.
2.7 Windows-
(Dual Pane)
Windows shall be installed in panels per customer drawing. Windows shall
be the picture-window type or sliding window type per customer drawing.
The window glass shall be a minimum 3/16-inch thick clear, tempered
safety glass pre mounted in an aluminum frame. A 3-1/2” air gap
shall separate the two pieces of tempered glass for optimum sound and
temperature control. Windows shall be a nominal 40 inches in height
and extend across the full width of its supporting panel. The windowsill
height shall be 41 inches from the floor. The sliding windows shall
be able to slide sideways. The sliding windows shall have locks lockable
from the inside of the modular office. Weather stripping shall also
be provided with the sliding windows.
2.8 Panel
Caps
Anodized aluminum panel caps or manufacturer’s standard panel
caps incorporating a vertical fascia shall be installed securely on
the top perimeter of the wall panels. The panel caps shall provide a
neat appearance where the wall panels and roof deck come together.
3.0 Doors
All doors shall be pre-hung at the factory and assembled into panels
to ensure easy installation and proper fit. Doors shall be a nominal
36 inches wide by 80 inches high and have thickness of 1-3/4 inches.
The interior and exterior finish of the doors shall be color coordinated
with the exterior finish of the wall panels. All doors shall have the
same finish on both sides. The type of door is as follows:
a. 3068 Steel door
with standard hinges and knob. Powder coated to coordinate with wall
color.
3.1 Single
Vision Lite / Window In Door (Single Pane)
The upper half of all doors shall have a 20" x 24" with a
minimum 3/16- Inch thick clear tempered safety glass picture window.
Rubber shall be placed on the inside of all openings
3.1 Single
Vision Lite / Window In Door (Dual Pane)
The upper half of all doors shall have a 20" x 24" with a
minimum 3/16- Inch thick clear tempered safety glass picture window.
Rubber shall be placed on the inside of all openings.
4.0 Panelized
Roof System
The roof system shall be an aluminum roll-formed interlocking panel.
The roof deck panels shall be a minimum of .19 gauge thickness with
a rigid polystyrene core permanently laminated to aluminum skin. Panels
shall be designed to achieve optimum structural efficiency. The Panelized
roof shall span the full width of the modular guardhouse and hold a
minimum of 30 psf. live load and 10 psf. dead load and shall conform
to seismic zone 4 requirements. The roof shall be installed with a minimum
of 1/4” per ft grade on the overall span.
5.0 Hardware
Hardware shall be Allied Modular Standard.
6.0 Ceiling
The ceiling shall be suspended from the roof deck and supported by the
wall perimeter or in accordance with the manufacturer’s standard
installation procedures. The suspended ceiling shall consist of white
enameled T-bar ceiling grid hung from hanger tabs and 12 gauge wires,
mineral fiber tiles with a random-fissured finish. The ceiling panels
shall be 2 feet wide by 4 feet long by minimum 5/8-inch thick lay-in
acoustical panels or equivalent. The ceiling structure shall meet UL
Class A Fire Rating with 0-25 flame spread. The T-bar ceiling grid shall
provide support for the light fixtures and shall be supported at each
corner of each light fixture.
7.0 Heat
/ Air Conditioner & Opening
Appropriate size wall mounted A/C or HVAC shall be provided in accordance
with all local mechanical codes. A Heating/Ventilation/Air Conditioner
(HVAC) panel shall be located per customer. The HVAC opening shall be
of solid construction. The HVAC opening shall be reinforced to support
a minimum 150-pound wall mounted HVAC unit and shall be lined with aluminum
trim. There shall be at least 60 inches between the floor and the bottom
of the HVAC opening.
8.0 Light
Fixtures - T12
Light fixtures shall be recessed in the ceiling. The lay-in light fixtures
shall be 2 feet wide by 4 feet long and incorporate T12 4100K lamps
with electronic ballasts. Light fixtures shall have a minimum 128-watt
capacity and be equipped with diffuser lens. The appropriate quantity
of light fixtures shall be located in the ceiling such that a minimum
of 50-foot candles lighting at a height of 3 feet from the floor is
evenly maintained throughout the modular office. Tubes shall be provided
by other.
8.1 Light
Fixtures - T8
Light fixtures shall be recessed in the ceiling. The lay-in light fixtures
shall be 2 feet wide by 4 feet long and incorporate T8 4100K lamps with
electronic ballasts. Light fixtures shall have a minimum 128-watt capacity
and be equipped with diffuser lens. The appropriate quantity of light
fixtures shall be located in the ceiling such that a minimum of 50-foot
candles lighting at a height of 3 feet from the floor is evenly maintained
throughout the modular office. Tubes shall be provided by other.
8.1.1 Light
Switches
A light switch shall be provided at each doorway. Light switches shall
be located on the interior wall and opposite the door hinges. Light
switches shall be conveniently placed for easy access. Light switches
shall be located 42 inches in height from the floor. Light switches
shall be provided with cover plates. Light switches shall conform to
the National Electric Code.
8.2 Electrical
Outlets
Wall outlets shall be standard 110-volt AC duplex outlets. Wall outlets
shall be located as shown on drawings. Wall outlets shall be a nominal
18 inches in height from the floor. A 230-volt outlet shall be installed
near the HVAC opening at a height of at least sixty inches to interface
with the HVAC power cords. Outlets shall be provided with cover plates.
Light switches shall conform to the National Electric Code.